SPECIFICATIONS OF MATERIALS FOR WATER MAINS AND
SERVICES |
|
|
|
|
|
PIPE: Ductile Iron, Class 52 per Specifications
AWWA C151; C111 (Push-on Joint); C104 cement lining (inside) and asphaltic
coatings (outside) and 2 brass wedges per joint. |
|
|
|
|
|
FITTINGS: Cast or Ductile Iron per Specifications
AWWA C110; C153; C111 (Mechanical Joint); C104 cement lining (inside) and
asphaltic coatings (outside) with two (2) each mechanical joint retainer
kits/fitting. |
|
|
|
|
|
FITTINGS (HYDRANT): In addition to "Fittings"
Specifications, hydrant tees shall be anchoring type; Manufacturer: Clow
F-1217 or approved equal. All exposed
bolts to be stainless steel grade 304. |
|
|
|
|
|
VALVES: Gate Valves AWWA C509; C111 (Mechanical
Joint); OPEN CLOCKWISE; Manufacturer:
Kennedy Kenseal II or approved equal with two (2) each mechanical
joint retainer kits/valve. All
exposed bolts to be stainless steel grade 304. |
|
|
HYDRANTS: AWWA C502, C111 (Mechanical Joint
connection - 6"); OPEN COUNTER CLOCKWISE; 5 1/2' bury, 2-2 1/2" and
1-4" outlets, 4 1/2" bottom valve opening, painted red with yellow
bonnett and nozzle caps. (Private
hydrants are to be painted red.)
Hydrant thread and operating nuts shall conform to "UTICA",
"WHITESTOWN", or other threading as approved by the Mohawk Valley
Water Authority for the area being serviced.
Manufacturer: Kennedy K-81A. |
|
|
|
|
|
VALVE BOXES: "Buffalo" style - 5 ¼” diameter,
3 piece screw type, size D with No. 6 base. |
|
|
|
|
|
TAPPING SLEEVES and
TAPPING VALVES: Clow F-5205
and F-5093 or approved equal (furnished and installed by Mohawk Valley Water
Authority per established fee schedule).
“Fast Taps” not allowed. All
exposed bolts to be stainless steel grade 304. |
|
|
|
|
|
SERVICE LINES: Following service line materials for
3/4" or 1" size Corporations Stop:
Mueller H-15000 or approved equal (furnished and installed by Mohawk
Valley Water Authority per established fee schedule). |
|
|
|
|
|
|
COPPER TUBING: Type K, ASTM B88 (Use 3/4" diameter
when pressure is greater than 50 psi; use 1" for pressure less than 50
psi). |
|
|
|
|
|
CURB STOPS: Mueller H-15204 or approved equal at
property line. |
|
|
|
|
|
CURB BOXES: Buffalo Type, 2 1/2" Shaft, three
piece screw type, size 95E or approved equal; which provides full inside
diameter access to the curb stop. |
|
|
|
|
|
PRESSURE REGULATOR: Required when water pressure exceeds 70
psi - installed downstream of water meter.
|
|
|
|
|
|
BACKFLOW PREVENTOR: Appropriate protection as required by
Engineering Department. Application
required. |
|
|
|
|
|
METER PIT: Required when distance from tap to building
entry point is more than 200 feet for residential sites, or 300 feet for
commercial structures. |